Charge Signal Disconnect Safety¶
To ensure safety and compliance with industry standards, both CCS and MCS charge controllers incorporate a hardware-level safety mechanism that immediately disconnects the vehicle's contactors upon the loss of critical charge signals, such as CP (Control Pilot) for CCS or CE (Charge Enable) for MCS.
This rapid response, designed to meet strict timing requirements outlined in standards like IEC 61851-23, prevents potential hazards associated with uncontrolled power flow during charging.
By directly triggering a hardware-based disconnect, the EVCC guarantees a fast and reliable emergency shutdown, safeguarding the user, the vehicle and the charging infrastructure from possible damage or electrical incidents.
Lock safety (Avoid inlet disconnection on load)¶
The lock of the inlet is here to prevent exposing users to dangerous electrical potentials.
When the charge controller is managing an inlet lock, in abnormal situations it might decide to keep it locked if it sees the situation is dangerous, OR if it has no way of assessing if the situation is dangerous or not.
While these is for safety sake, it can also lead to user frustration. In such event, an inlet lock should be manually unlocked only either by technicians able to assess the situation and the risks. Or in case of remote assistance, the user should be guided by a remote technician in such a way it can assess the situation remotely.
A restart/power cycle of the charge controller might also automatically resolve the issue. But only if the controller is able to assess the situation by itself.
Safe conditions¶
Fundamentally, the controller needs the following conditions to command an unlock:
- DC contactors must be open. This itself implies the reported flowing current is less than or equal to 1 A.
- The reported inlet voltage is less than or equal to 60 V.
- The information about contactor status, flowing current and inlet voltage are all reliable. That means it should have received them within the last can_timeout_ms milliseconds.
During an abnormal event that persists outside of a normal communication session with a charger, the controller spawns an "emergency monitor" and will stay in that state until the situation resolves. Part of the emergency monitor is to look for these above conditions, and command the contactors and inlet lock as needed.
Usually, a lock would remain locked when:
- The charger keeps producing voltage or current despite all the "emergency stop" signaling.
- The contactors are not opening (eg. they could be welded, or their control is inoperative).
- The CAN bus is in a bad state (eg. disconnected, physically severed, overloaded, too noisy).
- The lock control is inoperative.
- Unrecoverable crash of the controller applications.
Note
Upon restart, power cycle, or any cycling back to Waiting_For_EVSE state, if the controller sees
the lock feedback tells it is locked, it will assess the situation before commanding an unlock.
Ie. If after a reboot the abnormal situation is resolved, the lock will be released. But if it is not (ie. still high voltage at the inlet), or if the controller is "blind" (eg. CAN bus is in a bad state) then it will not unlock.